MAD-481

Addressable control module of 1 relay output voltage free of 240 Vac and 5A which provides a non-resettable contact C, NO, NC. It takes one loop address. Requires 24 Vdc auxiliary powers. LED status indicator. Connection through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-ONE. Consumption less than 300μA at rest. Allows installation without polarity. Red color. Dimensions: 100 x 82 x 23 mm.

Category: Tags: ,

Description

The range of MAD-400 modules has been developed to offer a wide and complete range of input and
output ports to be used with Detnov’s addressable fire control panels.
The MAD-400 modules allow performances and manoeuvres for the proper functioning of the fire
detection system, monitoring and/or acting according to the needs of the installation.
The MAD-400 modules have been designed to facilitate their installation process and they may be
installed using screws or fitted into a DIN rail. Each module is equipped with removable terminal
blocks and a LED status indicator. The addressing of the modules ir carried out through the PGD-200
programmer or auto addressing for isolator version.
The MAD-481 module provides 1 free voltage relay output to switch loads up to 230VAC and 5A on and
off. It provides an independent NC circuit and an independent NO circuit.
The MAD-481 module take the power supply directly from the loop and assigned a number of loop
addresses according to the number of inputs available in the module.
All the range of MAD-400 modules can be installed inside the BOX-ONE and BOX-SIX boxes